Relay and Buzzer Operation

Synergy can be configured to trigger the ARB Module's internal relays and buzzer if specified sensors go into alarm; this is configured by creating a Sensor Group in Synergy, adding the required sensors, assigning the required Local Alarms to the Sensor Group and then selecting the Relay output in the associated Local Alarms.

When an alarm in the associated Sensor Group occurs the ARB Module's relays will switch contacts; the normally open relay closes, the normally closed relay opens, and the buzzer will sound.

Cancel Relays

Relay operation for the current alarm(s) can be canceled by pressing the Cancel Relay Operation button adjacent to the power connector; this will cancel the relays operation until a new alarm occurs.

Silence Buzzer

Pressing the Mute key will silence the buzzer until a new alarm occurs.

 

MS1000 Card Operation

Synergy can be configured to switch outputs on MS1000 cards, connected to the ARB Module's RS485 Bus, if specified sensors go into alarm, as follows:

1.Create a Sensor Group in Synergy.

2.Add the required Sensors to the Sensor group.

3.Assign the required Local Alarms to the Sensor Group.

4.Select the required MS1000 Channel Number for the Relay output.

When an alarm in the associated Sensor Group occurs, the MS1000 Relay output will switch; this can be used to drive a sound alarm, beacon or auto-dialer.